Back to main page Atlanta Appliances repair, Inc.
Dehumidifiers Repair
D
ehumidifiers are household appliances that remove moisture (humidity) from anarea. Humidity is defined as the amount of water vapor in the air and is measured
in terms of relative humidity (RH %). The higher the RH percentage, the more water
vapor in the air. The optimum relative humidity level in an area is generally considered to be
between 30 percent and 50 percent. Humidity levels exceeding 50 percent with temperatures
over 70 degrees Fahrenheit can be uncomfortable, unhealthy, and in most cases cause personal
property damage. Anything above this range may promote bacteria growth or mold. In colder
climates, during the heating season, humidity levels should be maintained between 30 percent
and 40 percent to prevent moisture from collecting or condensing on the windows and doors.
Dehumidifiers (Figure 30-1) were designed to remove unwanted moisture from the air in
a given area.
Sizing a Dehumidifier
Dehumidifiers, when properly set, can maintain the desired humidity level in that area.
The capacity is usually measured in pints per 24 hours and is determined by two factors: the
square footage of the space that needs to be dehumidified and the conditions that exist in
the space before dehumidification. Table 30-1 depicts a dehumidifier sizing chart.
Another measure that can determine the size of dehumidifier the consumer needs is the
amount of air the appliance can move over a certain period of time. Dehumidifiers measure
this in cubic feet per minute (CFM). The CFM is an important measure for dehumidification
because the unit can only extract moisture from the air that passes through the dehumidifier.
All of the air in a room must flow through the dehumidifier in order to remove moisture.
To calculate the CFM you need from the dehumidifier, multiply the cubic feet of the area by
the recommended air changes per hour (ACH) in Table 30-1, and then divide that number
by 60 minutes. The resulting number is the CFM the dehumidifier should have.
Principals of Operation
A refrigeration system (Figure 30-2) is used to collect the moisture from the air. The dehumidifier
may have either a reciprocating (split phase) or a rotary (permanent split capacitor) compressor
that circulates the refrigerant in the dehumidifier. The evaporator operating temperatures
are around 33 to 37 degrees Fahrenheit. When moisture-ladened air passes over the
1135
CHAPTER
1136
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sFIGURE 30-1
A typical portable
dehumidiier.
Condition Without
Dehumidification
500
Sq. Ft.
1,000
Sq. Ft.
1,500
Sq. Ft.
2,000
Sq. Ft.
2,500
Sq. Ft.
3,000
Sq. Ft.
In humid weather, the area is
moderately damp and it has
a musty odor. (6070% RH)
ACH=3
10 pints 14 pints 18 pints 22 pints 26 pints 30 pints
In very damp areas, it always
feels damp and spots appear
on the walls and floors.
(7080% RH) ACH=4
12 pints 17 pints 22 pints 27 pints 32 pints 37 pints
In areas that are very wet,
the walls and the floor are
sweating or there is seepage.
(8090% RH) ACH=5
14 pints 20 pints 26 pints 32 pints 38 pints 44 pints
In areas that are extremely
wet; wet floor, laundry room,
high-load conditions.
(90100% RH) ACH=6
16 pints 23 pints 30 pints 37 pints 44 pints 51 pints
The higher the humidity in an area, the more often the air should cycle through the dehumidifier. This is known as
Air Changes per Hour, or ACH.
TABLE 30-1
Dehumidifier Sizing GuidelinesPART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1137evaporator, the moisture will collect on the evaporator coil and condense into a liquid. The
cool air is then drawn through the condenser coil and warms the air before it is recirculated
back into the room area. The water collected on the evaporator coil will run off the coil into
a bucket. Many dehumidifier models include a built-in in humidistat, a device that allows
the consumer to set the humidity level desired for that room. Once the room reaches the
desired humidity level, the dehumidifier will cycle on and off automatically to maintain
that RH level.
Safety First
Any person who cannot use basic tools or follow written instructions should
not attemptto install, maintain, or repair any dehumidifiers. Any improper installation, preventive
maintenance, or repairs could create a risk of personal injury or property damage. If you do
not fully understand the installation, preventive maintenance, or repair procedures in this
chapter, or if you doubt your ability to complete the task on your dehumidifier, please call
your service manager.
This chapter covers the electrical components and how to diagnose the sealed system.
The actual repair or replacement of any sealed-system component is not included in this
chapter. It is recommended that you acquire refrigerant certification (or call an authorized
service company) to repair or replace any sealed-system component, as the refrigerant in
the sealed system must be recovered properly.
Before continuing, take a moment to refresh your memory on the safety procedures in
Chapter 2.
Dehumidifiers in General
Much of the troubleshooting information in this chapter covers dehumidifiers in general,
rather than specific models, in order to present a broad overview of service techniques. The
illustrations that are used in this chapter are for demonstration purposes only to clarify the
description of how to service these appliances. They in no way reflect a particular brands
reliability.
FIGURE 30-2
A typical refrigeration
system used in a
dehumidiier. The air
is drawn in through
the evaporator and
expelled out through
the contender coil
by a fan.
Suction tube
Discharge tube
Capillary tube
Collected water
Air
low
(out)
Air
low
(in)
Condenser
Fan
Evaporator
1138
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sLocation and Installation of a Dehumidifier
When installing the dehumidifier in the home, you must allow 12 inches of space on all sides
of the dehumidifier so that air can circulate properly (see Figure 30-3). The dehumidifier can
be installed on the floor, table, or shelf. When installing the dehumidifier on a table or shelf,
make sure the table or shelf can support the weight of the dehumidifier, including the weight
of the bucket full of water. Next, plug the dehumidifier into a 120 volt properly grounded
receptacle, properly polarized.
Safety note: Do not use an extension cord with the dehumidifier.Dehumidifier Maintenance
The dehumidifiers coils should be chemically cleaned at least annually to remove the dirt
and slime buildup within the unit. Clean the outer case and cabinet (Figure 30-4a) with a
soft cloth and a mild detergent. Next, vacuum the grille, or use a brush on the grill. Do not
use abrasives or bleach on the dehumidifier. About once a month, remove the water bucket
and clean it to avoid growth of mold, mildew, and bacteria. Dont forget to wash the air
filter and shake off the excess water and let it air dry, and then reinstall it (Figures 30-4b and c)
at least once a month also.
Step-by-Step Troubleshooting by Symptom Diagnosis
When servicing a dehumidifier, dont overlook the simple things that might be causing
the problem. Step-by-step troubleshooting by symptom diagnosis is based on diagnosing
malfunctions, with possible causes arranged into categories relating to the operation of the
dehumidifier. This section is intended only to serve as a checklist to aid you in diagnosing
a problem. Look at the symptom that best describes the problem you are experiencing with
the dehumidifier, and then correct the problem.
12''
12''
FIGURE 30-3
Place the dehumidiier
within 12 inches of
any walls or other
blockages that might
prevent proper air
circulation.
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1139Dehumidifier Will Not Run (No Fan, No Compressor)
Check control settings.
Check voltage to the unit.
Check bucket; it may be full of water.
Check wiring.
Run diagnostics; you may have bad humidistat.
Check the humidity level in the room and compare that reading against thecontrol setting.
Condenser Fan Motor Runs (Compressor Not Running)
Check the de-icer thermostat on mechanical models.
Check thermistor on electronic models.
On electronic models, run diagnostics; replace electronic control board.
Check compressor overload and relay.
Check compressor windings.Condenser Fan Motor Does Not Run (Compressor Is Running)
Check voltage going to condenser fan motor.
Test the condenser fan motor windings.
Check condenser fan blade.Condenser Fan Motor and Compressor Running (Evaporator Coil Frozen Up)
Check the room temperature (nonde-icer models); the room temperature must behigher than 65 degrees Fahrenheit. Frost should disappear within 60 minutes. If not,
check the sealed system.
FIGURE 30-4
Performing maintenance on the dehumidiier. Clean the outside of the unit (a), front grille (b), andilter (c).
(a) (b) (c)
1140
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sCondenser Fan Motor and Compressor Running (No Dehumidification)
Dehumidifier may have a sealed-system problem.
Test the humidity in the room; might have low humidity in area.
Check the air filter.
Check the evaporator coil. Is it clean?Dehumidifier Is Running (Insufficient Dehumidification)
Check and make sure that the grilles are not obstructed.
Check air filter.
Check the evaporator coil. Is it clean?
Run diagnostics on the sealed system; it might have a low refrigerant charge.
Check the room size. The dehumidifier might be too small for the square footage.
Check and make sure that the doors and windows are closed.
Check the room temperature.Dehumidifier Runs Continuously
Check the control settings.
Check the room humidity level; may have to adjust humidity setting.Repair Procedures
Each repair procedure is a complete inspection and repair process for a single dehumidifier
component. It contains the information you need to test and replace components.
Electronic Components
The electronic components consist of the following: electronic control board and touchpad.
The typical complaints associated with the electronic components are:
Unable to program the touchpad panel functions.
The display board will not display anything.
Unusual display readouts.
Unable to control the relative humidity.
The compressor will not run.
The condenser fan motor will not run.To prevent electrostatic discharge (ESD) from damaging expensive electronic
components, follow the steps in Chapter 11.
To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by operating the dehumidifier controls.Turn off the electricity to the dehumidifier, and wait for two minutes before turning
it back on. If a fault code appears, look up the code. If the dehumidifier will not
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1141power up, locate the technical data sheet behind the control panel for diagnostics
information. It will be helpful if you can locate the actual service manual for the
dehumidifier model you are working on to properly diagnose the dehumidifier. The
service manual will assist you in properly placing the dehumidifier in the service
test mode for testing the dehumidifier functions.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is there electricity to the dehumidifier? The voltage at the wall
receptacle must be within ±10 percent of the voltage rating on the model and serial
data plate. Do you have the correct polarity? (See Chapter 6.) Is the electrical
receptacle polarized and properly grounded?
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity. This can be done by pulling the plug out of the wall receptacle. Or disconnect
the electricity at the fuse panel or circuit breaker panel. Turn off the electricity.
W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access to the electronic components. You can gain access to the electroniccomponents by removing the front grille and the screws on the control panel
(Figures 30-5a, b, c, and d). Next, tilt the control panel away from the dehumidifier,
making sure not to pull any of the wires off the controls.
W
ARNING Do not touch the wiring or capacitor until it is discharged. A capacitor will holda charge indefinitely, even when it is not currently in use. A charged capacitor is extremely
dangerous. Discharge all capacitors immediately any time that work is being conducted in their
vicinity. Redischarge after repowering the equipment if further work must be done. Many
capacitors are internally fused. If you are not sure, you can use a 20,000 ohm 2-watt resistor to
discharge the capacitor. Do not use a screwdriver to short out the capacitor. By doing so, you will
blow out the fuse in the capacitor and the capacitor will not work. Safely use an insulated pair of
pliers to remove the wires from the capacitor and place the resistor across the capacitor terminals.
When checking a dual capacitor with a capacitor analyzer or ohmmeter, you must test both sides
of the capacitor.
5.
Test the electronic components. If you are able to run the dehumidifier test mode,check the different functions of the dehumidifier. Use the technical data sheet for
the model you are servicing to locate the test points on the wiring schematic. Check
all wiring connections and wiring. Using the technical data sheet, test the electronic
control and display board, input voltages, and output voltages.
6.
Remove the defective component. To remove the defective component, remove thescrews that secure the printed circuit board to the dehumidifier console frame.
Disconnect the connectors from the electronic control board and display.
1142
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sTop cover
screws
Rear of
dehumidiier
(a) (b)
(d)
(e) (f)
Front
screws
Float actuator
Front grille
screws
Rear of
dehumidiier
(c)
FIGURE 30-5
This igure depicts how to gain access to the components. Remove the bucket and screwsas shown.
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
11437.
Install the new component. To install a new component, just reverse the disassemblyprocedure and reassemble. Reinstall all panels and the front grille and bucket.
Then, restore the electricity to the dehumidifier. Test the dehumidifier operation.
To prevent ESD from damaging expensive electronic components, simply follow the
steps in Chapter 11.
Capacitor
A capacitor is a device that stores electricity to provide an electrical boost for motor starting.
Most high-torque motors need a capacitor connected in series with the start winding circuit
to produce the desired rotation under a heavy starting load. The capacitor can also be used
for motor efficiency.
The typical complaints associated with failure of the capacitor are:
Fuse is blown or the circuit breaker trips.
Fan motor will not run.
Fan motor has a burning smell.
Motor or compressor tries to start and then shuts off on overload.To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by operating the dehumidifier. Listencarefully, and you will hear if there are any unusual noises or if the circuit breaker
trips. If you smell something burning, immediately turn off the dehumidifier and
pull out the plug. It will be helpful if you can locate the actual service manual for
the dehumidifier model you are working on to properly diagnose the dehumidifier.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is the dehumidifier installed properly? Does it have the correct
voltage? The voltage at the wall receptacle must be within ±10 percent of the
voltage rating on the model and serial data plate. Do you have the correct polarity?
(See Chapter 6.)
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity. This can be done by pulling the plug from the electrical outlet. Be
sure that you only remove the dehumidifier plug. Or disconnect the electricity at
the fuse panel or at the circuit breaker panel. Turn off the electricity.
W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access to the capacitor. Some models have the capacitor mounted on the fanmotor; on other models, it is mounted behind the electrical controls. Remove the
front grille and filter. Some units have either a one-piece or a two-piece grille with
locking tabs and/or screws (see Figures 30-5 and 30-6). On other models, you should
be able to gain access by removing the screws that secure the control panel to the
dehumidifier frame.
1144
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sW
ARNING Do not touch the wiring or capacitor until it is discharged. A capacitor will holda charge indefinitely, even when it is not currently in use. A charged capacitor is extremely
dangerous. Discharge all capacitors immediately any time that work is being conducted in their
vicinity. Redischarge after repowering the equipment if further work must be done.
5.
Test the capacitor. Many capacitors are internally fused. If you are not sure, you canuse a 20,000 ohm 2-watt resistor to discharge the capacitor. Do not use a screwdriver
to short out the capacitor. By doing so, you will blow out the fuse in the capacitor
and the capacitor will not work. Safely use an insulated pair of pliers to remove the
wires from the capacitor and place the resistor across the capacitor terminals. When
checking a dual capacitor with a capacitor analyzer or ohmmeter, you must test
both sides of the capacitor. Set the ohmmeter on the highest scale and then place
one probe on one terminal and the other probe on the other terminal (Figure 29-15).
Observe the meter action. While the capacitor is charging, the ohmmeter will read
nearly zero ohms for a short period of time. Then the ohmmeter reading will slowly
return toward infinity. If the ohmmeter reading deflects to zero and does not return
to infinity, the capacitor is shorted and should be replaced. If the ohmmeter reading
remains at infinity and does not dip toward zero, the capacitor is open and should
be replaced.
To test for a grounded capacitor, leave one meter probe on the capacitor terminal,
and attach the other probe to the outer casing of the capacitor or dehumidifier
chassis ground. There should be no reading if the capacitor is not grounded. Next,
remove the probe from the capacitor terminal, and place the probe on the other
terminal. Again, there should be no reading indicated if the capacitor is not
grounded.
FIGURE 30-6
A typical dehumidiier
without its panels
attached.
Condenser
fan motor
Control
panel
Compressor
Run capacitor
Evaporator and
condenser coils
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1145When using a capacitor analyzer to test capacitors, it will show whether the capacitor
is open or shorted. It will tell whether the capacitor is within its microfarads
rating and it will show whether the capacitor is operating at the proper power-factor
percentage. The instrument will automatically discharge the capacitor when the test
switch is released.
6.
Remove the capacitor. Remove the capacitor from its mounting bracket.7.
Install a new capacitor. To install the new capacitor, just reverse the disassemblyprocedure and reassemble.
N
OT E A capacitor is rated by its working voltage (WV or WVac) and by its storage capacity inmicrofarads (μF). Always replace a capacitor with one that has the same voltage rating and the
same (or up to 10 percent greater) microfarad rating.
Fan Motor
Dehumidifiers use a single fan motor with a single shaft for the fan blade or blower wheel.
The typical complaints associated with failure of the fan motor are:
No air is blowing out of the discharge grille.
When the motor runs, there are loud noises.
The fuse or circuit breaker trips when the air conditioner is started.To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by operating the dehumidifier. Listencarefully, and you will hear if there are any unusual noises or if the circuit breaker
trips. It will be helpful if you can locate the actual service manual for the
dehumidifier model you are working on to properly diagnose the dehumidifier.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is the dehumidifier installed properly? Does it have the correct
voltage? The voltage at the wall receptacle must be within ±10 percent of the
voltage rating on the model and serial data plate. Do you have the correct polarity?
(See Chapter 6.)
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity. This can be done by pulling the plug out of the wall receptacle. Be
sure that you only remove the dehumidifier plug. Or disconnect the electricity at
the fuse panel or at the circuit breaker panel. Turn off the electricity.
W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access to the fan motor. Before you begin to remove the fan motor, testthe motor windings. Remove the outer wrapper and the front grille and filter
(Figures 30-5 and 30-6).
1146
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e sW
ARNING Do not touch the wiring or capacitor until it is discharged. A capacitor will holda charge indefinitely, even when it is not currently in use. A charged capacitor is extremely
dangerous. Discharge all capacitors immediately any time that work is being conducted in their
vicinity. Redischarge after repowering the equipment if further work must be done. Many
capacitors are internally fused. If you are not sure, you can use a 20,000 ohm 2-watt resistor to
discharge the capacitor. Do not use a screwdriver to short out the capacitor. By doing so, you will
blow out the fuse in the capacitor and the capacitor will not work. Safely use an insulated pair of
pliers to remove the wires from the capacitor and place the resistor across the capacitor terminals.
When checking a dual capacitor with a capacitor analyzer or ohmmeter, you must test both sides
of the capacitor.
5.
Disconnect the motor wire leads. Disconnect the motor wire leads from the controlpanel, and label them. Check the motor windings for continuity (Figure 30-6). Using
the wiring diagram, check for resistance on the condenser fan motor windings. To
check for a grounded winding in the motor, take the ohmmeter probes and check
from each motor wire lead to the motor housing. The ohmmeter will indicate
continuity if the windings are grounded.
Finally, spin the motor shaftit should turn freely. If the shaft is hard to turn,
replace the fan motor. Now move the motor shaft in an up-and-down motion
perpendicular to the motor body. The shaft should have virtually no movement.
If there is a lot of play in the end bell bearings, replace the fan motor.
16.
Remove the fan motor. To remove the fan motor (Figure 30-6), remove the screwsthat hold the fan motor bracket in place. Then, remove the fan blade or blower wheel.
Depending on which model you are servicing, the removal of the fan motor will
vary from manufacturer to manufacturer. However, the basic steps are the same for
every dehumidifier.
N
OT E Replace the fan motor with a duplicate of the original for easier installation.N
OT E With the fan motor removed from the unit, it is the perfect time to chemically clean theremainder of the dehumidifier. Everything will be exposed, and it will be easier to clean the unit.
7.
Reinstall the fan motor. To reinstall the fan motor, just reverse the instructions instep 6, and reassemble. When you reinstall the condenser fan blade, make sure to
place it back on the motor shaft in the same position. Before reinstalling the outer
cabinet on the dehumidifier, test the dehumidifier first. Make sure the fan blade or
the blower wheel is not hitting against anything.
Compressor and Overload Protector
The compressor (reciprocating or rotary type) is the heart of the vapor compression system.
It is used to circulate the refrigerant throughout the sealed system. The overload is attached
to the compressor housing. The overload protects the compressor. Some models are equipped
with a relay to assist the compressor in starting.
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1147The typical complaints associated with failure of the compressor are:
The dehumidifier does not run at all.
The compressor makes a humming or buzzing noise and stops.
The circuit breaker trips when the dehumidifier starts up.To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by asking the customer to describe whatthe dehumidifier is doing. It will be helpful if you can locate the actual service
manual for the dehumidifier model you are working on to properly diagnose the
dehumidifier.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is the dehumidifier installed properly? Does it have the correct
voltage? Check for a voltage drop during dehumidifier startup. The voltage at the
wall receptacle must be within ±10 percent of the voltage rating on the model and
serial data plate. Do you have the correct polarity? (See Chapter 6.)
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity. This can be done by pulling the plug from the receptacle. Or disconnect
the electricity at the fuse panel or at the circuit breaker panel. Turn off the electricity.
W
ARNING Before you begin to service any high-voltage components within the dehumidifier, youmust discharge the high-voltage capacitors first.
W
ARNING A capacitor will hold a charge indefinitely, even when it is not currently in use.A charged capacitor is extremely dangerous. Discharge all capacitors immediately any time that
work is being conducted in their vicinity. Redischarge after repowering the equipment if further
work must be done. Many capacitors are internally fused. If you are not sure, you can use a
20,000 ohm 2-watt resistor to discharge the capacitor. Do not use a screwdriver to short out the
capacitor. By doing so, you will blow out the fuse in the capacitor and the capacitor will not
work. Safely use an insulated pair of pliers to remove the wires from the capacitor and place the
resistor across the capacitor terminals. When checking a dual capacitor with a capacitor analyzer
or ohmmeter, you must test both sides of the capacitor.
W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access to the compressor. To access the compressor, remove the outer cabinet(Figures 30-5 and 30-6). This will expose the compressor, fan motor, and electrical
controls (Figure 30-6). Next, remove the compressor terminal cover (Figure 29-20)
by removing the retaining nut or clip that secures the cover. Remove the terminal
cover and washer.
1148
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e s5.
Test the overload protector. To test the overload protector, remove the wires fromthe overload and compressor terminals. Next, place the probes of the ohmmeter on
the overload terminals (see Figure 29-20). Set the meter scale on R
Χ 1. The readingwill show continuity. If not, replace the overload protector.
6.
Test the compressor. The compressor terminals are marked C, S, and R: C indicatesthe common winding terminal, S indicates the start winding terminal, and R
indicates the run winding terminal. Refer to the wiring diagram for the model that
you are servicing. Set the meter scale on R
Χ 1, touch the probes together, and adjustthe needle setting to indicate a zero reading. Next, place the probes of the ohmmeter
on the terminals marked S and R (see Figure 25-37a). The meter reading will show
continuity. Now place the meter probes on the terminals marked C and S. The meter
reading will show continuity. Finally, place the meter probes on the terminals
marked C and R. The meter reading will show continuity. The total number of ohms
measured between S and R is equal to the sum of C to S plus C to R. The compressor
should be tested for proper resistance, as indicated on the wiring diagram.
To test the compressor for ground, place one probe on a compressor terminal, and attach
the other probe to the compressor housing or to any good ground (see Figure 25-37b). Set
the meter scale to R
Χ 1000. The meter reading will show no continuity. Repeat this for theremaining two terminals. The meter reading will show no continuity. If you get a continuity
reading from any of these terminals to ground, the compressor is grounded. Replace it.
Bucket Switch
The bucket switch is a single-pole, double-throw (SPDT) device that shuts off the dehumidifier
when the bucket is full of water. The switch is mounted to the frame directly behind the bucket
(Figure 30-7). The switch is activated by the float assembly.
The typical complaints associated with failure of the bucket switch are:
The dehumidifier does not run at all.
Water spills out of the dehumidifier.Float
(a)
Bucket
switch
(b)
FIGURE 30-7
Do not run the
dehumidiier without
the bucket. (a) The
loat assembly. (b) The
loat switch in the rear
of the dehumidiier.
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1149To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by asking the customer to describe whatthe dehumidifier is doing. It will be helpful if you can locate the actual service
manual for the dehumidifier model you are working on to properly diagnose the
dehumidifier.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is the dehumidifier installed properly? Does it have the correct
voltage? Check for a voltage drop during dehumidifier startup. The voltage at the
wall receptacle must be within ±10 percent of the voltage rating on the model and
serial data plate. Do you have the correct polarity? (See Chapter 6.)
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity. This can be done by pulling the plug from the receptacle. Or disconnect
the electricity at the fuse panel or at the circuit breaker panel. Turn off the electricity.
W
ARNING Before you begin to service any high-voltage components within the dehumidifier, youmust discharge the high-voltage capacitors first.
W
ARNING A capacitor will hold a charge indefinitely, even when it is not currently in use.A charged capacitor is extremely dangerous. Discharge all capacitors immediately any time that
work is being conducted in their vicinity. Redischarge after repowering the equipment if further
work must be done. Many capacitors are internally fused. If you are not sure, you can use a
20,000 ohm 2-watt resistor to discharge the capacitor. Do not use a screwdriver to short out the
capacitor. By doing so, you will blow out the fuse in the capacitor and the capacitor will not
work. Safely use an insulated pair of pliers to remove the wires from the capacitor and place the
resistor across the capacitor terminals. When checking a dual capacitor with a capacitor analyzer
or ohmmeter, you must test both sides of the capacitor.
W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access and removal of the bucket switch and float. Pull the bucket toward you,releasing the actuator from the float assembly (Figures 30-5a and b). Remove the outer
wrapper to gain access to the bucket switch (Figure 30-6). To remove the float assembly,
pull the pin (Figure 30-8), and remove the float assembly. To remove the bucket
switch assembly (Figure 30-9a), squeeze the tabs to remove the bucket switch.
5.
Test the bucket switch. Use the ohmmeter to test the resistance between the threeterminals on the switch. Figure 30-9b shows testing between common and normally
open terminals. In the switch rest position, there will be maximum resistance. From
common to the normally closed terminal, there should be zero resistance. When the
bucket switch lever is depressed, common to the normally open terminals, there
should be zero resistance. From the common to the normally closed terminals, you
should have a reading of maximum resistance.
1150
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e s6.
Install the new component. To install a newcomponent, just reverse the disassembly procedure
and reassemble. Reinstall all panels and the front
grille and bucket. Then, restore the electricity to the
dehumidifier. Test the dehumidifier operation. To
prevent ESD from damaging expensive electronic
components, simply follow the steps in Chapter 11.
Defrost Thermostat
The defrost thermostat is mounted on the suction line
(Figure 30-10).
The typical complaints associated with failure of the
defrost thermostat (heat pump models only) are:
Ice buildup on the outdoor coil.
The air conditioner will not heat.To handle these problems, perform the following steps:
1.
Verify the complaint. Verify the complaint by checking the control setting. Turn thecontrol to the highest setting for heat, and then turn it back to a normal setting to
see if the dehumidifier starts heating. It will be helpful if you can locate the actual
service manual for the dehumidifier model you are working on to properly
diagnose the dehumidifier.
2.
Check for external factors. You must check for external factors not associated withthe dehumidifier. Is the dehumidifier installed properly? Explain to the user how to
set the controls. The voltage at the wall receptacle must be within ±10 percent of the
voltage rating on the model and serial data plate. Do you have the correct polarity?
(See Chapter 6.)
3.
Disconnect the electricity. Before working on the dehumidifier, disconnect theelectricity to the unit. This can be done by pulling the plug from the receptacle.
Or disconnect the electricity at the fuse panel or at the circuit breaker panel. Turn off
the electricity.
Pin
FIGURE 30-8
Pull the pin to release theloat assembly.
Normally
open
Normally
closed Common
FIGURE 30-9
(a) Squeeze the tabs to release the bucket switch. (b) SPST bucket switch. Use theohmmeter to test the switch contacts.
(a) (c)
PART VI
C h a p t e r 3 0 : D e h u m i d i f i e r s
1151W
ARNING Some diagnostic tests will require you to test the components with the power turned on.When you disassemble the control panel or remove the outer cabinet, you can position the panel
in such a way that the wiring will not make contact with metal. This will allow you to test the
components without electrical mishaps.
4.
Gain access to the defrost thermostat. To access the defrost thermostat, remove theouter wrapper and the front grille and filter (Figures 30-5 and 30-6). Next, tilt the
control panel away from the dehumidifier, making sure not to pull any of the wires
off the controls. The manufacturer placed the defrost thermostat control on the
suction line (Figure 30-10). The defrost thermostat is a nonadjustable thermostat
without a stem or knob attached to it. On other models, the defrost thermostat
might be a bimetal thermostat that is clamped to the end of the evaporator coil with
two wires coming out of it that lead back to the control panel.
W
ARNING Do not touch the wiring or capacitor until it is discharged. A capacitor will holda charge indefinitely, even when it is not currently in use. A charged capacitor is extremely
dangerous. Discharge all capacitors immediately any time that work is being conducted in their
vicinity. Redischarge after repowering the equipment if further work must be done. Many
capacitors are internally fused. If you are not sure, you can use a 20,000 ohm 2-watt resistor to
discharge the capacitor. Do not use a screwdriver to short out the capacitor. By doing so, you will
blow out the fuse in the capacitor and the capacitor will not work. Safely use an insulated pair of
pliers to remove the wires from the capacitor and place the resistor across the capacitor terminals.
When checking a dual capacitor with a capacitor analyzer or ohmmeter, you must test both sides
of the capacitor.
FIGURE 30-10
Defrost thermostat
attached to the
suction line. When the
evaporator goes below
37 degrees
Fahrenheit, the defrost
thermostat opens,
shutting off the
compressor. The
condenser fan motor
will continue to run.
When the suction
line temperature
rises to 59 degrees
Fahrenheit, the defrost
thermostat closes
and the compressor
starts up.
Suction line to
compressor
Defrost
thermostat
1152
P a r t V I : A p p l i a n c e S e r v i c e , I n s t a l l a t i o n , a n d P r e v e n t i v e M a i n t e n a n c e P r o c e d u r e s5.
Test the defrost thermostat. To test the defrostthermostat, disconnect the wires from the
defrost thermostat terminals on the control
panel, label them, and place the ohmmeter
probes on the terminals (see Figure 29-6b). Set
the range scale on R
Χ 1, and test the thermostatfor continuity. If the temperature is above
60 degrees Fahrenheit, the resistance reading
will be zero, indicating that the contacts are
closed. Now, place the thermostat in a bucket of
ice. With the ohmmeter leads still attached, the
contacts should open when the temperature
drops below 37 degrees Fahrenheit.
6.
Remove the thermostat. With the thermostatexposed and the wires already removed, the
defrost thermostat must now be removed from
the suction line. The thermostat is held in place
on the suction line with a spring load clamp (Figure 30-11). Remove the thermostat
clamp. If the clamp comes off the suction line, remember where the clamp goes
back. The placement of the clamp and thermostat is crucial for the dehumidifier to
function properly.
7.
Install a new thermostat. To install the new defrost thermostat, just reverse theorder of disassembly and reassemble. Then test the defrost thermostat by running
the dehumidifier. Just remember to reinstall the bimetal clamp in the same location
from which it was removed. If you do not, the dehumidifier will not cycle properly.
Wiring Diagrams and Schematics
The wiring diagrams and schematics that are used in this chapter might be helpful to
diagnose a dehumidifier (see Figures 30-12, 30-13, 30-14, 30-15, and 30-16). These diagrams
are not a substitution for the exact wiring schematic that might be on the inside cover of the
outer wrapper.
Endnote
1. When the bearings wear out in the end bell of the